Form 416 (01.13) ©SOR Inc.
1/8
These instructions provide information for installation and
field calibration of B Temperature Switches.
Process temperature changes cause proportional
vapor pressure changes in the temperature sensing
bulb that acts on a diaphragm/piston assembly to
actuate and deactuate a snap-action electrical switching
element at discrete process temperatures. The instrument’s
behavior is determined by vapor pressure (105 range model
fill media is inert gas). For best results with the SOR
®
thermal activated temperature switch, the entire probe
must experience the media being monitored. If a
thermowell is being used, a thermal paste is recommended
to ensure the transfer of heat through the well to the probe.
B Temperature Switches
General Instructions
Registered Quality System to ISO 9001
Design and
specifications are
subject to change
without notice.
For latest revision, go to
www.sorinc.com
Table of Contents
Installation ....................................... 2
SIL Installation ..................................2
Electrical Connection ...........................3
Calibration .......................................3
Dimensions ......................................4
Operation.........................................6
ATEX Marking Information .....................7
Declaration of Conformity .....................8
n
and
i
n
g
ment’s
e
model
®
b
e
m
ended
probe
.
NOTE: If you suspect that a product is defective, contact the factory
or the SOR Representative in your area for a return authorization
number (RMA). This product should only be installed by trained
and competent personnel.
Zobrazit stránku 0
1 2 3 4 5 6 7 8

Shrnutí obsahu

Strany 1 - B Temperature Switches

Form 416 (01.13) ©SOR Inc. 1/8These instructions provide information for installation and field calibration of B Temperature Switches.Process temperat

Strany 2 - Installation

2/8Form 416 (01.13) ©SOR Inc. Remote-Mount Probe — CapillarySecure a housing-mounting pad to bulkhead, panel rack or pipe stanchion with suitable 1/4”

Strany 3 - Electrical Connection

Form 416 (01.13) ©SOR Inc. 3/8CalibrationElectrical ConnectionEnsure that wiring conforms to all applicable local and national electrical codes and in

Strany 4 - B-Series

4/8Form 416 (01.13) ©SOR Inc. Dimensions 3/4” hex set point adjusting nut Calibration scale Housing mounting pad See g and for temperature sensi

Strany 5 - Contact the factory for

Form 416 (01.13) ©SOR Inc. 5/8Dimensions are for reference only.Contact the factory for certified drawings for a particular model number.Linear = mm/i

Strany 6 - Operation

6/8Form 416 (01.13) ©SOR Inc. For ATEX Certi ed ModelsMaximum Surface TemperatureT6 Rating - 85oCT5 Rating - 100oCOperationDesignatorAdjustable Range

Strany 7 - ATEX Marking Information

Form 416 (01.13) ©SOR Inc. 7/8ATEX Marking InformationFor ATEX Certi ed ModelsManufacturer’sRegistered TrademarkATEX Listing InformationThread Form I

Strany 8 - of Conformity

8/8Form 416 (01.13) ©SOR Inc. Declaration of ConformityFor ATEX Certi ed ModelsForm 1380 (08.12) ©2012 SOR Inc. (Printed in USA) ProductManufacturerD

Komentáře k této Příručce

Žádné komentáře