Form 771 (08.13) ©SOR Inc.
1/20
The Ultrasonic Point Level Control indicates liquid presence/absence within a sensor cavity.
Two piezoelectric crystals face each other across the sensor cavity. One crystal transmits
an ultrasonic signal; the other crystal receives the signal.
When the sensor cavity is empty, the receiver detects a weak signal because air is a poor
conductor of ultrasonic waves. The yellow LED is lit, indicating 8 mA current output.
When process liquid fills the sensor cavity, the receiver detects a strong signal because
liquids are good conductors of ultrasonic waves. The red LED is lit, indicating 16 mA
current output.
The Ultrasonic Point Level Control constantly monitors sensor integrity and changes the
current output in the unlikely event of a sensor failure. The Failure Mode Switch located
inside the control housing can be field selected to either 5 mA or 19 mA to indicate
sensor failure.
Remote Self-Test is provided with non-intrinsically safe units only. Units equipped with
two terminal blocks feature the remote self-test. A dry contact may be used up to 50
feet/15 meters from the control to simulate a sensor failure.
Standard 316SS and Te on Notch-Type sensors, epoxy tip-sensitive, and 316SS viscous
sensors are available for use with the point level control. Extreme care must be taken when
installing units with Teflon
®
sensors. See installation instructions beginning on page 2.
Ultrasonic Two-Wire
Point Level Control
General Instructions
Registered Quality System to ISO 9001
Design and
specifications are
subject to change
without notice.
For latest revision,
go to sorinc.com
NOTE: If you suspect that a product is defective, contact the factory or the SOR
®
Representative
in your area for a return authorization number (RMA). This product should only be installed by
trained and competent personnel.
Table of Contents
Installation ....................................... 3
Remote Cable Connection .....................4
Remote Electrical Connection ................4
Electrical Connection ...........................5
Calibration and Function Test .................8
Sensor Replacement ...........................9
Circuit Board Replacement ....................9
CE Marked Units .............................. 10
Control Drawings ............................. 11
Troubleshooting ............................... 16
Dimensions ................................ 17-19
Zobrazit stránku 0
1 2 3 4 5 6 ... 19 20

Shrnutí obsahu

Strany 1 - Point Level Control

Form 771 (08.13) ©SOR Inc. 1/20The Ultrasonic Point Level Control indicates liquid presence/absence within a sensor cavity. Two piezoelectric crystals

Strany 2 - Installation

10/20Form 771 (08.13) ©SOR Inc. Model NumberAccessory DesignatorI.S. CI, FI or AI Expf FM or CSNon-Agency (no match)721 2-N-P9-G5003-009 5003-

Strany 3

Form 771 (08.13) ©SOR Inc. 11/20Control Drawing

Strany 4 - Remote Cable Connection

12/20Form 771 (08.13) ©SOR Inc. Control Drawing

Strany 5 - Electrical Connection

Form 771 (08.13) ©SOR Inc. 13/20Control Drawing

Strany 6

14/20Form 771 (08.13) ©SOR Inc. Control Drawing

Strany 7 - Install bead as close as

Form 771 (08.13) ©SOR Inc. 15/20Control Drawing

Strany 8 - Calibration and Function Test

16/20Form 771 (08.13) ©SOR Inc. TroubleshootingSymptom/ProblemPossible Cause Corrective ActionNo current in the loopNo LEDs lit.1. Power supply turned

Strany 9 - Circuit Board Replacement

Form 771 (08.13) ©SOR Inc. 17/20DimensionsMetal SensorK2 HSGADD FOR2.0050.8K1 HSG210.8 *8.30A93.3 *3.6715.90.63116.74.5996.03.7895.33.7520.60.8122.20.

Strany 10 - CE Marked Units

18/20Form 771 (08.13) ©SOR Inc. Te on SensorDimensions are for reference only.Contact the factory for certified drawings for a particular model numbe

Strany 11 - Control Drawing

Form 771 (08.13) ©SOR Inc. 19/20Viscous SensorDimensions are for reference only.Contact the factory for certified drawings for a particular model numb

Strany 12

2/20Form 771 (08.13) ©SOR Inc. InstallationNotch-Type and Epoxy Sensors (Series 371-N and 371-E)Ultrasonic Level Sensors can be mounted by inserting t

Strany 13

20/20Form 771 (08.13) ©SOR Inc. 14685 West 105th Street, Lenexa, KS 66215  913-888-2630  800-676-6794 USA  Fax 913-888-0767Registered Quality

Strany 14

Form 771 (08.13) ©SOR Inc. 3/20Open Sump or BasinDo not suspend the unit by rigid conduit installed in the electrical hub. When installing the unit ov

Strany 15

4/20Form 771 (08.13) ©SOR Inc. Remote Electrical ConnectionRemote Cable ConnectionConduit must be installed between the sensor base and the electronic

Strany 16 - Troubleshooting

Form 771 (08.13) ©SOR Inc. 5/20Discharge the SensorTemperature changes which occur during shipment may result in a small electrical charge inside the

Strany 17 - Dimensions

6/20Form 771 (08.13) ©SOR Inc. Electrical Connection (Remote Self-Test)Ensure that wiring comforms to all applicable local and national electrical cod

Strany 18 - Te on Sensor

Form 771 (08.13) ©SOR Inc. 7/20Electrical Connection (Intrinsically Safe)Intrinsically Safe Models (does not apply to viscous or epoxy controls and s

Strany 19 - Viscous Sensor

8/20Form 771 (08.13) ©SOR Inc. Calibration and Function TestNo calibration is needed. Units are calibrated at the factory. No user adjustments are req

Strany 20 - Form 771 (08.13) ©SOR Inc

Form 771 (08.13) ©SOR Inc. 9/20Current Output ChartYellow LED (Dry)Red LED (Wet)Current Meter (+ 1mA)Sensor StatusFailure Mode8 mA Dry__16 mA Wet_

Komentáře k této Příručce

Žádné komentáře